DVC-V304 VAV Controller (Single Duct,Programmable,No Actuator,3 UIs,4 BOs,MS/TP)
BACnet Device Profile
BACnet Advanced Application Controller (B-AAC)
External Inputs
1 10K Thermistor or Dry Contact
2 Universal Inputs (10-bit) supporting:
0-5 VDC
0-10 VDC
10 kΩ Thermistor
4-20 mA
Dry Contact (using 10 kΩ Thermistor jumper setting)
Internal Inputs
1 Actuator position feedback (optional)
1 Air flow sensor, true differential pressure, 0 to 1 inH2O (0 to 248.8 Pa)
External Outputs
4 Binary TRIAC Outputs
Internal Outputs
2 Binary Outputs for damper open and close
Belimo Actuator
45 in-lbs. (nominal torque)
Less than 35 db (A) noise level
Siemens Actuator
44 in-lbs. (nominal torque)
Less than 35 db (A) noise level
Device Addressing
Set via DIP switch and jumpers or software setup
Connectors
Removable screw-type terminal connectors
Wiring Class
Class 2
Tubing
Flow sensor tubing must be ⁵⁄₃₂ in. inside diameter
Power
24 VAC 50/60 Hz @ 15 VA (not including output loading, 52 VA max with fully loaded TRIAC Outputs)
Power (UL864)
24 VAC 50/60 Hz @ 15 VA (52 VA Max with fully loaded TRIAC Outputs)
Technology
16-bit processor
1 MB (8-megabit) flash memory
128 KB SRAM memory for database
Communications Ports
Main LAN
RS-485 NET1
BACnet MS/TP up to 76800 bps, max 99 devices per port
SubLAN
RS-485 NET2
Delta LINKnet up to 76800 bps, max 4 devices on LINKnet with no more than 2 DFM devices
Optional Modbus up to 38400 bps, max 5 devices
Ambient
32° to 131°F (0 to 55°C)
10 to 90% RH (non-condensing)
Dimensions
9⅜ x 4¾ x 3⅛ in. (23.9 x 12.0 x 8.0 cm) with housing
Weight
1.85 lb. (840 g) with housing and actuator
Compliance
CE
FCC
Listings
UL 916 Listed
C-UL Listed
BTL Listed
UL 864 Listed for UL 864 product numbers